Applications
- Ideal for use with Elkor Technologies Inc. Power Meters:
- WattsOn Power Transducer
- WattsOn-Mark II Advanced Energy Meter
- Current Transformers for the i-Spy AC Current Transducer.
- Current Transformers for the i-Snail-X AC Current Transducer.
- Secondary current transformers applied on 5 A leads of the existing CTs
Specifications
MCTA |
MCTB |
|
Maximum Current | 300A | 450A |
Output @ Max. Input | 120mA (no burden) | 112.5mA (no burden) |
Turns Ratio | 3000:1 | 4000:1 |
Wire Window Inside Diameter (D1) | 0.77" (19.5mm) | 1.28" (32.5mm) |
Outside Diameter (D2) | 1.87" (47.5mm) | 2.33" (59.0mm) |
Linearity | 0.1% (from 1A to 300A) | 0.1% (from 1A to 450A) |
Phase Shift | < 0.05° | < 0.02° |
Leads | 2m (6.5'), 600V rated | 45cm (18"), 600V rated |